Possible Cause: System has not been balanced.
            Corrective Action: Request a copy of the balance report and review against the specified CFM requirements.
           
          
            Possible Cause: The filter is dirty.
            Corrective Action: Replace the filter.
           
          
            Possible Cause: The coil is dirty.
            Corrective Action: Clean the coils. Brushes, water, cleaning solutions designed for HVAC coils, and air are acceptable cleaning methods. Do not use a pressure washer.
           
          
            Possible Cause: A blockage exists in the system.
            Corrective Action: Verify that all dampers are open. Check for restrictions in the ductwork.
           
         
          
            
              Possible Cause: System losses are greater than design.
              Corrective Action: Adjust or change sheaves or replace motor as necessary based on the system losses as installed.
             
            
              Possible Cause: Fan speed is lower than design, belt slipping, or wrong sheaves.
              Corrective Action: Adjust the belt and sheaves as necessary for the installed conditions.
             
            
              Possible Cause: Fan is running backwards.
              Corrective Action: Switch two legs of power at unit main power supply (all unit components are phased at the factory).
             
            
              Possible Cause: VFD requires adjustment.
              Corrective Action: Check fan set points. Adjust PID settings for desired performance.